Matrix Installation and Operation
To configure alarm inputs, follow the steps below:
1. In the Alarm menu, select the Alarm Input Sense option.
2. In the Alarm Input Sense screen, use the numeric keys to enter the number of the
alarm input to be configured and press the ENTER key to jump to it. The up/down
joystick commands can also be used to move through the inputs.
3. Using the right joystick command, select N/O to configure the alarm input as a
normally-open contact or select N/C to configure it as a normally-closed contact.
4. Repeat steps 2 and 3 to set all alarm inputs as required.
5. Once selections on this screen are complete, select the Return to Alarm Menu to
return to the previous menu.
Configuring Auxiliary Outputs
Auxiliary outputs can be connected to the MegaPower LT in a normally-open or a normally-
closed rest state. An auxiliary output will operate in a rest state until it is triggered, at
which point it will switch to the active state.
Once connected, an auxiliary output can be added to alarm responses so that when an
alarm or event occurs, the auxiliary output will switch to the active state (see page 36).
The Alarm Output Sense menu is reserved for future use. Currently, changing the settings
in this menu will have no effect on the operation of the MegaPower LT.