SPEEDDOME ULTRA VII EIS DAY/NIGHT CAMERA DOME 8200-0184-14, REV. A
INSTALLATION AND SERVICE GUIDE
7 of 37
Cable Requirements
Data Cable
The table below shows requirements for
SensorNet, RS-422, and Manchester networks. For
more information about communication protocols
and cable networks, see Communication Protocols
and Cable Networks, 8000-2573-19.
Data cable requirements
SensorNet RS-422 Manchester
Cable type 1
unshielded,
twisted
pair*
2
shielded,
twisted
pair*
1
shielded
twisted
pair**
Wire gauge 22 AWG 22 AWG 18 AWG
Connection Non-
polarized
Polarized Polarized
Max.
devices on
line
32 10 3
* Power, data, and video cables can be ordered
separately or within a composite cable that can be
ordered in various lengths. Plenum-rated cables must
be used in indoor ceilings used for environmental air
return (called "other air space" in the National Electrical
Code). Order parts through your distribution network.
Note: If you order cable from an outside source, wire
colors may be different.
** Belden 88760 (plenum), or Belden 8760 cable (non-
plenum) cable is recommended. Plenum-rated cables
must be used in indoor ceilings used for environmental
air return (called "other air space" in the National
Electrical Code). Order
cable directly from Belden by
calling 1-800-235-3361.
Power Cable
For the camera dome to operate properly, line
voltage must not go below the worst-case low line
voltage shown in the following table. Make cable
lengths as short as possible to minimize affects of
low line voltages. As shown in the table, maximum
cable length depends on the Class 2 LPS (low
voltage) ac source (such as a J-box) and the worst-
case low line voltage. These lengths are for
Sensormatic composite cables, which use 18
AWG
ac power wires.
Note: Typically, distances are used that provide
a 15% margin between nominal and low line
conditions. For example, if the nominal voltage is
120Vac, restrict cable length to that associated
with 100Vac (0.85 x 120).
Worst-case ac line voltages
Indoor Dome
Worst-Case Meters
AC Power Source
Low Line V (Feet)
28 VA
117 180 (600)
Transformer
100 130 (430)
5604-0006-01
90 80 (270)
50 VA
117 180 (600)
Transformer
100 150 (500)
5604-0044-01
90 90 (300)
1-position SensorNet
117 210 (700)
RJ1SNUD
100 130 (430)
90 100 (325)
1-position SensorNet
117 210 (700)
RJ1SNUD-1
100 130 (430)
90 100 (325)
117 300 (1000)
6-position SensorNet
100 230 (750)
Indoor J-Box
90 160 (530)
RJ6SN
240 300 (1000)
200 230 (750)
180 160 (530)
10-Position RS-422
117 275 (900)
Indoor 120V/60Hz J-Box
100 200 (650)
RJ860AP
90 130 (430)
10-Position RS-422
240 275 (900)
Indoor 240V/60Hz J-Box
200 200 (650)
RJ860AP1
180 130 (430)
Universal Transformer
117 200 (650)
0300-0914-01
100 130 (430)
90 90 (300)
Universal Transformer
240 200 (650)
0300-0914-03
200 130 (430)
180 90 (300)